Please use this identifier to cite or link to this item: https://repositorio.ufjf.br/jspui/handle/ufjf/12088
Files in This Item:
File Description SizeFormat 
jhonatannascimentodacosta.pdfPDF/A3.01 MBAdobe PDFThumbnail
View/Open
Type: Tese
Title: Avaliação do impacto da intermitência da geração eólica na estabilidade de tensão de sistemas elétricos de potência utilizando um método de análise de sensibilidade
Author: Costa, Jhonatan Nascimento da
First Advisor: Passos Filho, João Alberto
Referee Member: Castro Junior, Carlos Alberto de
Referee Member: Melo, Igor Delgado de
Referee Member: Londero, Rafael Rorato
Referee Member: Costa, Vander Menengoy da
Referee Member: Peres, Wesley
Resumo: Este trabalho aborda, em uma primeira etapa, o controle de tensão e frequência em redes elétricas contendo geração eólica. Para tanto, quatro tipos distintos de geradores eólicos são modelados matematicamente e então incluídos em uma formulação de fluxo de potência capaz de representar a regulação primária de frequência da rede. Além disso, uma estratégia de Controle Coordenado da Tensão terminal para fazendas eólicas compostas por Geradores Síncronos de Imãs Permanentes é apresentada. Esta estratégia permite controlar a magnitude da tensão terminal dessas fazendas eólicas e ajustar as gerações de potência reativa desses geradores eólicos. Para isso, fatores de participação são utilizados nesta estratégia de controle. Eles são calculados com base nos limites máximos de geração de potência reativa das máquinas que participam do controle de tensão. Estudos de casos mostram que os geradores eólicos podem ajudar na regulação primária de frequência dos sistemas e que a estratégia de controle de tensão proposta pode evitar a violação prematura dos limites de geração de potência reativa dos Geradores Síncronos de Imãs Permanentes. Este trabalho avalia, em uma segunda etapa, o impacto da característica intermitente da geração eólica na estabilidade de tensão dos Sistemas Elétricos de Potência. Para tanto, sensibilidades lineares e quadráticas da Margem de Carregamento com relação à velocidade do vento são calculadas. Estas sensibilidades baseiam-se nas equações inseridas em uma formulação do fluxo de potência capaz de representar a regulação secundária de frequência. Com estas sensibilidades, alterações na Margem de Carregamento devido a perturbações na velocidade do vento nas fazendas eólicas podem ser estimadas. Além disso, uma sensibilidade das variáveis de estado no Ponto de Máximo Carregamento do sistema com relação à velocidade do vento é também obtida durante o cálculo da sensibilidade quadrática. Com esta sensibilidade das variáveis de estado, a geração de potência ativa dos geradores síncronos após perturbações na velocidade do vento nas fazendas eólicas pode ser estimada. Nas análises efetuadas nesta segunda parte do trabalho dois tipos de geradores eólicos são considerados, os Geradores de Indução Duplamente Alimentados e os Geradores Eólicos de Velocidade Fixa Regulados por Stall (do inglês: travamento). Estimativas precisas da Margem de Carregamento são obtidas nos estudos de casos em redes contendo estes tipos de geradores eólicos, demonstrando a eficácia da metodologia proposta.
Abstract: This work addresses, in a first step, the voltage and frequency control in electrical networks containing wind generation. To this end, four distinct types of wind generators are mathematically modeled and then included in a power flow formulation capable of representing the primary frequency regulation of the grid. In addition, a Coordinated Voltage Control strategy for wind farms composed of Permanent Magnet Synchronous Generators is presented. This strategy allows controlling the magnitude of the terminal voltage of these wind farms and adjusting the reactive power generations of these wind generators. For this purpose, participation factors are used in this control strategy. They are calculated based on the maximum limits of reactive power generation of the machines that participate in the voltage control. Case studies show that wind generators can assist in the primary frequency regulation of the systems and that the proposed voltage control strategy can avoid the premature violation of the reactive power generation limits of the Permanent Magnet Synchronous Generators. This work evaluates, in a second stage, the impact of the intermittent characteristic of the wind generation on the voltage stability of the Electric Power Systems. For this purpose, linear and quadratic sensitivities of the Loading Margin with respect to the wind speed are calculated. These sensitivities are based on the equations inserted into a power flow formulation capable of representing the secondary frequency regulation. With these sensitivities, changes in the Loading Margin due to wind speed perturbations in the wind farms can be estimated. In addition, a sensitivity of the state variables at the system Maximum Loading Point with respect to the wind speed is also obtained during the calculation of the quadratic sensitivity. Based on this sensitivity, the active power generation of the synchronous generators after wind speed perturbations in the wind farms can be estimated. In the analyses performed in this second part of the work two types of wind generators are considered, the Doubly Fed Induction Generators and the Stall Regulated Fixed Speed Wind Generators. Precise estimates of the Loading Margin are obtained in the case studies in networks containing these types of wind generators, demonstrating the effectiveness of the proposed methodology.
Keywords: Geração eólica
Análise de sensibilidade
Margem de carregamento
Estabilidade de tensão
Wind generation
Sensitivity analysis
Loading margin
Voltage stability
Electric power systems
CNPq: CNPQ::ENGENHARIAS::ENGENHARIA ELETRICA
Language: por
Country: Brasil
Publisher: Universidade Federal de Juiz de Fora (UFJF)
Institution Initials: UFJF
Department: Faculdade de Engenharia
Program: Programa de Pós-graduação em Engenharia Elétrica
Access Type: Acesso Aberto
Attribution-NonCommercial-NoDerivs 3.0 Brazil
Creative Commons License: http://creativecommons.org/licenses/by-nc-nd/3.0/br/
URI: https://repositorio.ufjf.br/jspui/handle/ufjf/12088
Issue Date: 20-Dec-2019
Appears in Collections:Doutorado em Engenharia Elétrica (Teses)



This item is licensed under a Creative Commons License Creative Commons